<?xml version="1.0" encoding="UTF-8"?><rss version="2.0"
	xmlns:content="http://purl.org/rss/1.0/modules/content/"
	xmlns:wfw="http://wellformedweb.org/CommentAPI/"
	xmlns:dc="http://purl.org/dc/elements/1.1/"
	xmlns:atom="http://www.w3.org/2005/Atom"
	xmlns:sy="http://purl.org/rss/1.0/modules/syndication/"
	xmlns:slash="http://purl.org/rss/1.0/modules/slash/"
	>

<channel>
	<title>Sustainability Archivi - Techniconsult</title>
	<atom:link href="https://tcfirenze.com/category/sustainability/feed/" rel="self" type="application/rss+xml" />
	<link>https://tcfirenze.com/category/sustainability/</link>
	<description>Un unico partner nel settore Life Sciences</description>
	<lastBuildDate>Fri, 07 Jun 2024 07:23:27 +0000</lastBuildDate>
	<language>it-IT</language>
	<sy:updatePeriod>
	hourly	</sy:updatePeriod>
	<sy:updateFrequency>
	1	</sy:updateFrequency>
	<generator>https://wordpress.org/?v=6.9.4</generator>

<image>
	<url>https://tcfirenze.com/wp-content/uploads/2024/01/cropped-TC-FAVICON-32x32.png</url>
	<title>Sustainability Archivi - Techniconsult</title>
	<link>https://tcfirenze.com/category/sustainability/</link>
	<width>32</width>
	<height>32</height>
</image> 
	<item>
		<title>Strategie circolari nell&#8217;industria delle Life Science</title>
		<link>https://tcfirenze.com/strategie-circolari-nellindustria-delle-life-science/</link>
		
		<dc:creator><![CDATA[Pier Angelo Galligani]]></dc:creator>
		<pubDate>Fri, 07 Jun 2024 07:21:58 +0000</pubDate>
				<category><![CDATA[Sustainability]]></category>
		<guid isPermaLink="false">https://tcfirenze.com/?p=2074</guid>

					<description><![CDATA[<p>La circolarità e la valutazione del ciclo di vita sono pilastri fondamentali della sostenibilità nell'industria farmaceutica, essenziali...</p>
<p>L'articolo <a href="https://tcfirenze.com/strategie-circolari-nellindustria-delle-life-science/">Strategie circolari nell&#8217;industria delle Life Science</a> proviene da <a href="https://tcfirenze.com">Techniconsult</a>.</p>
]]></description>
										<content:encoded><![CDATA[<div class="wpb-content-wrapper"><div data-parent="true" class="vc_row row-container" id="row-unique-0"><div class="row triple-top-padding triple-bottom-padding single-h-padding limit-width row-parent"><div class="wpb_row row-inner"><div class="wpb_column pos-top pos-center align_left column_parent col-lg-12 single-internal-gutter"><div class="uncol style-light"  ><div class="uncoltable"><div class="uncell no-block-padding" ><div class="uncont"><div class="uncode_text_column text-lead" ><p>La circolarità e la valutazione del ciclo di vita sono pilastri fondamentali della sostenibilità nell&#8217;industria farmaceutica, essenziali per minimizzare il nostro impatto ambientale. Questo approccio olistico richiede un&#8217;esaminazione accurata di ogni fase del ciclo di vita dei beni e dei materiali, dall&#8217;estrazione della materia prima allo smaltimento o al riciclo. Abbracciando la circolarità, miriamo a ottimizzare l&#8217;uso delle risorse, ridurre i rifiuti e mitigare il nostro impatto sul pianeta.</p>
<p>Per implementare efficacemente i principi della circolarità, dobbiamo prima comprendere l&#8217;intricato tessuto dei processi di produzione e le loro ripercussioni ambientali. Questo include la considerazione di materiali e beni in entrata e in uscita, nonché degli effluenti solidi, liquidi e gassosi. Anche i servizi ausiliari e le funzioni, come quelli all&#8217;interno della catena di approvvigionamento e dei controlli di qualità, svolgono un ruolo cruciale nell&#8217;equazione della circolarità.</p>
<p>Dato il livello di complessità nell&#8217;analizzare gli impatti ambientali lungo l&#8217;intero ciclo di vita, l&#8217;utilizzo di strumenti software diventa prezioso. Questi strumenti ci consentono di analizzare una vasta gamma di dati relativi a materiali e beni, facilitando la presa di decisioni informate e l&#8217;ottimizzazione.</p>
<p>Nel settore farmaceutico, la circolarità si manifesta in vari ambiti:</p>
<ul>
<li><strong>Selezione dei Materiali:</strong> A partire dalla fase di progettazione, favorire materiali riutilizzabili o riciclabili e quelli provenienti da fonti di energia rinnovabile. I materiali per l&#8217;imballaggio, noti per il loro impatto ambientale, dovrebbero essere prevalentemente riciclabili.</li>
<li><strong>Pratiche di Progettazione delle Strutture:</strong> Ottimizzare la progettazione delle strutture per massimizzare il riutilizzo e il riciclo. Questo include strategie come il riutilizzo del condensato di vapore e i circuiti chiusi per lo scambio di calore, insieme alla minimizzazione delle perdite e all&#8217;utilizzo di risorse locali come l&#8217;acqua di pozzo.</li>
<li><strong>Pratiche Operative e di Manutenzione:</strong> Implementare meccanismi robusti di smistamento dei rifiuti e programmi di manutenzione preventiva per prolungare la vita delle attrezzature e ridurre le perdite di materiali. La formazione degli operatori è essenziale per massimizzare l&#8217;efficienza durante i processi di produzione.</li>
<li><strong>Conoscenza Migliorata dei Processi Produttivi:</strong> Utilizzare tecnologie come la Tecnologia Analitica dei Processi per perfezionare i processi produttivi e ottimizzare l&#8217;uso delle risorse.</li>
</ul>
<p>Un significativo onere ambientale all&#8217;interno delle strutture farmaceutiche deriva dagli effluenti solidi, liquidi e gassosi. È imperativo trattarli in conformità con le normative locali e adottare pratiche che ne minimizzino l&#8217;impatto. I rifiuti solidi dovrebbero essere riciclabili laddove possibile, con eccezioni per i rifiuti speciali che richiedono un trattamento specifico. Le tecnologie di incenerimento possono convertire i rifiuti solidi in una fonte di energia termica, mentre gli effluenti liquidi dovrebbero subire una purificazione prima dello smaltimento. Le emissioni gassose devono essere sottoposte a un adeguato trattamento prima del rilascio nell&#8217;atmosfera, con la ricircolazione dell&#8217;aria alimentata laddove conforme alle normative.</p>
<p>Inoltre, una valutazione completa del ciclo di vita dovrebbe considerare la fase di decommissioning, mirando a minimizzare la contaminazione attraverso una selezione attenta dei materiali durante la fase di progettazione.</p>
<p>Raggiungere la circolarità richiede collaborazione interdisciplinare e competenze, promettendo significative riduzioni del nostro impatto ambientale nel medio e lungo termine. Abbracciare questi principi non solo protegge il nostro pianeta, ma garantisce anche la sostenibilità delle nostre operazioni nell&#8217;industria farmaceutica.</p>
<p><a href="https://focus.pqegroup.com/sustainable-design-pharma-impactful-strategies-pqegroup-techniconsultgroup?utm_campaign=Sustainable%20Engineering&amp;utm_source=Direct%20Traffic&amp;utm_medium=Techniconsult%20group&amp;utm_term=Designing-your-sustainable-future">Scopri di più su come ottenere un impianto sostenibile</a></p>
</div></div></div></div></div></div><script id="script-row-unique-0" data-row="script-row-unique-0" type="text/javascript" class="vc_controls">UNCODE.initRow(document.getElementById("row-unique-0"));</script></div></div></div>
</div><p>L'articolo <a href="https://tcfirenze.com/strategie-circolari-nellindustria-delle-life-science/">Strategie circolari nell&#8217;industria delle Life Science</a> proviene da <a href="https://tcfirenze.com">Techniconsult</a>.</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>Verso un&#8217;industria farmaceutica più verde: Efficienza energetica</title>
		<link>https://tcfirenze.com/verso-unindustria-farmaceutica-piu-verde-efficienza-energetica/</link>
		
		<dc:creator><![CDATA[Pier Angelo Galligani]]></dc:creator>
		<pubDate>Fri, 19 Apr 2024 08:44:35 +0000</pubDate>
				<category><![CDATA[Sustainability]]></category>
		<guid isPermaLink="false">https://tcfirenze.com/?p=1961</guid>

					<description><![CDATA[<p>L'efficienza energetica è un principio guida ampiamente utilizzato nelle politiche dell'UE riguardanti l'ambiente e la sostenibilità…</p>
<p>L'articolo <a href="https://tcfirenze.com/verso-unindustria-farmaceutica-piu-verde-efficienza-energetica/">Verso un&#8217;industria farmaceutica più verde: Efficienza energetica</a> proviene da <a href="https://tcfirenze.com">Techniconsult</a>.</p>
]]></description>
										<content:encoded><![CDATA[<div class="wpb-content-wrapper"><div data-parent="true" class="vc_row row-container" id="row-unique-1"><div class="row triple-top-padding triple-bottom-padding single-h-padding limit-width row-parent"><div class="wpb_row row-inner"><div class="wpb_column pos-top pos-center align_left column_parent col-lg-12 single-internal-gutter"><div class="uncol style-light"  ><div class="uncoltable"><div class="uncell no-block-padding" ><div class="uncont"><div class="uncode_text_column text-lead" ><p>L&#8217;efficienza energetica è un principio guida ampiamente utilizzato nelle politiche dell&#8217;UE riguardanti l&#8217;ambiente e la sostenibilità, in quanto la sua applicazione contemporanea può garantire un consumo energetico primario più basso, minori perdite di distribuzione dell&#8217;energia, costi operativi ridotti e decarbonizzazione.</p>
<p>Innanzitutto, vale la pena sottolineare cosa significhi <strong>efficienza energetica</strong>. Secondo la norma EN ISO 50001:2018, l&#8217;efficienza energetica può essere definita come il rapporto tra un output (di prestazioni o energia, ecc.) e un input di energia. Quindi, l&#8217;efficienza può essere aumentata riducendo l&#8217;input, aumentando l&#8217;output o applicando una combinazione dei due.</p>
<p>Un concetto simile è chiaro quando si parla di macchine, poiché l&#8217;efficienza energetica coincide (più o meno) con l&#8217;efficienza del motore. Quest&#8217;ultima determina la differenza tra i valori di input e output.</p>
<p>Per quanto riguarda gli impianti di produzione, la<strong> complessità nel raggiungere l&#8217;efficienza energetica</strong> aumenta. Questo perché, sia i comportamenti del personale, che le operazioni delle attrezzature possono influenzare l&#8217;efficienza energetica dell&#8217;impianto e spesso, il consumo energetico non è accuratamente allineato con le effettive esigenze.</p>
<p>Questo aspetto può essere dovuto a sistemi di misurazione e controllo insufficienti e, di conseguenza, le operazioni non possono seguire istantaneamente i requisiti di utilizzo dell&#8217;energia. Inoltre, le attività controllate manualmente sono difficilmente riproducibili e il consumo correlato di solito non viene calcolato. Un&#8217;altra causa può essere il sovradimensionamento di impianti, macchinari e requisiti dell&#8217;utente.</p>
<p>Va notato che nel caso di sistemi di produzione di energia alimentati da combustibili fossili, un aumento dell&#8217;efficienza energetica promuove una riduzione delle emissioni di CO2 nell&#8217;atmosfera.</p>
<p><strong>Dalla teoria alla pratica</strong>, riportiamo la strategia adottata per migliorare l&#8217;efficienza energetica in un <strong>progetto greenfield relativo a una struttura di produzione di farmaci sterili</strong>.</p>
<p>Sono state applicate tre misure principali: il miglioramento dell&#8217;isolamento dell&#8217;involucro edilizio, il recupero di calore da un chiller per la produzione di acqua calda e la riduzione del flusso d&#8217;aria di alimentazione in aree classificate.</p>
<p>In dettaglio, la<strong> prima misura</strong> riguarda il miglioramento dell&#8217;isolamento dell&#8217;involucro edilizio. La normativa locale riporta i requisiti minimi per la trasmittanza termica in edifici nuovi o rinnovati, ma non sono obbligatori per gli impianti di produzione. Tuttavia, tali valori sono usati come riferimenti nel design. Questa scelta porta a una diminuzione del consumo annuo del 3% per l&#8217;elettricità e del 12% per il gas naturale.</p>
<p>La <strong>seconda misura di miglioramento dell&#8217;efficienza energetica</strong> riguarda il recupero di calore da un chiller per generare acqua calda per i sistemi HVAC invece di installare una caldaia a gas naturale dedicata. Il beneficio di questa scelta progettuale è una diminuzione rilevante del consumo di gas naturale, cioè -54% all&#8217;anno. D&#8217;altra parte, il recupero di calore dal chiller comporta un aumento del 7% del consumo di elettricità. Anche se i due effetti sono opposti, il beneficio complessivo è chiaro in termini di risparmio energetico e, in questo caso, anche decarbonizzazione.</p>
<p><strong>Infine</strong>, viene mostrata la diminuzione del flusso d&#8217;aria di alimentazione in aree classificate. Questa misura è composta da due diverse riduzioni: la riduzione durante le operazioni di produzione (periodi in funzione) e la successiva attenuazione nei periodi di riposo.</p>
<p>In dettaglio, durante la progettazione, il metodo generalmente adottato di impostare valori predeterminati di cambio d&#8217;aria per ora (ACH), basati sull&#8217;esperienza e considerazioni empiriche, viene sostituito da calcoli accurati dei flussi d&#8217;aria di alimentazione richiesti e dell&#8217;efficacia della ventilazione per ciascuna area. Quest&#8217;ultima viene valutata attraverso analisi di fluidodinamica computazionale (CFD) per gli spazi e le configurazioni più complessi.</p>
<p>Quindi, la riduzione e l&#8217;attenuazione del flusso d&#8217;aria risultano come conseguenza del metodo adottato e non implicano rischi di sicurezza o GMP. Tale misura determina benefici multipli: comporta non solo la diminuzione dell&#8217;energia per la ventilazione ma anche la riduzione del consumo energetico per il riscaldamento e il raffreddamento poiché il volume d&#8217;aria trattato diminuisce. Il risparmio energetico annuo dovuto a questa scelta progettuale ammonta al 8% del consumo complessivo di elettricità.</p>
<p>In sintesi, le misure di miglioramento dell&#8217;efficienza energetica riportate portano a una notevole riduzione del consumo di gas naturale e a una ulteriore diminuzione dell&#8217;energia elettrica utilizzata. Di conseguenza, <strong>si ottiene un risparmio complessivo del 32% del consumo energetico annuo</strong>.</p>
<p><a href="https://focus.pqegroup.com/sustainable-design-pharma-impactful-strategies-pqegroup-techniconsultgroup?utm_campaign=Sustainable%20Engineering&amp;utm_source=Direct%20Traffic&amp;utm_medium=Techniconsult%20group&amp;utm_term=Designing-your-sustainable-future">Scopri di più su come ottenere un impianto sostenibile</a></p>
</div></div></div></div></div></div><script id="script-row-unique-1" data-row="script-row-unique-1" type="text/javascript" class="vc_controls">UNCODE.initRow(document.getElementById("row-unique-1"));</script></div></div></div>
</div><p>L'articolo <a href="https://tcfirenze.com/verso-unindustria-farmaceutica-piu-verde-efficienza-energetica/">Verso un&#8217;industria farmaceutica più verde: Efficienza energetica</a> proviene da <a href="https://tcfirenze.com">Techniconsult</a>.</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>Come la simulazione CFD può supportare C.C.S., Q.R.M. e sostenibilità nelle strutture farmaceutiche</title>
		<link>https://tcfirenze.com/come-la-simulazione-cfd-puo-supportare-c-c-s-q-r-m-e-sostenibilita-nelle-strutture-farmaceutiche/</link>
		
		<dc:creator><![CDATA[Pier Angelo Galligani]]></dc:creator>
		<pubDate>Thu, 28 Sep 2023 15:54:25 +0000</pubDate>
				<category><![CDATA[Strumenti in-house]]></category>
		<category><![CDATA[Sustainability]]></category>
		<guid isPermaLink="false">https://tcfirenze.com/?p=667</guid>

					<description><![CDATA[<p>La simulazione della dinamica dei fluidi computazionale (CFD) si è affermata…</p>
<p>L'articolo <a href="https://tcfirenze.com/come-la-simulazione-cfd-puo-supportare-c-c-s-q-r-m-e-sostenibilita-nelle-strutture-farmaceutiche/">Come la simulazione CFD può supportare C.C.S., Q.R.M. e sostenibilità nelle strutture farmaceutiche</a> proviene da <a href="https://tcfirenze.com">Techniconsult</a>.</p>
]]></description>
										<content:encoded><![CDATA[<div class="wpb-content-wrapper"><div data-parent="true" class="vc_row row-container" id="row-unique-2"><div class="row limit-width row-parent"><div class="wpb_row row-inner"><div class="wpb_column pos-top pos-center align_left column_parent col-lg-12 single-internal-gutter"><div class="uncol style-light"  ><div class="uncoltable"><div class="uncell no-block-padding" ><div class="uncont"><div class="uncode_text_column" ><p>Nell’industria farmaceutica, l’adozione di strategie di controllo della contaminazione (CCS) e l’attuazione di adeguate misure di gestione dei rischi di qualità (QRM) sono fondamentali per le organizzazioni al fine di garantire la qualità e la sicurezza del prodotto. La simulazione della dinamica dei fluidi computazionale (CFD) si è affermata come uno strumento potente per fornire preziose informazioni sul flusso dei fluidi, il trasferimento di calore, la dispersione e il controllo della contaminazione all’interno dell’ambiente di produzione.</p>
<p>Oggi, oltre alla conformità alle GMP (Good Manufacturing Practices), l’ottimizzazione del consumo energetico e la riduzione della carbon footprint sono diventati importanti problemi a causa dei notevoli flussi d’aria di ventilazione richiesti per gli ambienti puliti e le aree classificate. Sfruttando la simulazione CFD nella progettazione dell’HVAC, le organizzazioni farmaceutiche possono supportare le strategie di controllo della contaminazione (CCS) e implementare pratiche robuste di gestione del rischio di qualità, garantendo in definitiva la produzione di prodotti farmaceutici sicuri ed efficaci e promuovendo le iniziative di sostenibilità.</p>
</div></div></div></div></div></div><script id="script-row-unique-2" data-row="script-row-unique-2" type="text/javascript" class="vc_controls">UNCODE.initRow(document.getElementById("row-unique-2"));</script></div></div></div><div data-parent="true" class="vc_row row-container" id="row-unique-3"><div class="row limit-width row-parent"><div class="wpb_row row-inner"><div class="wpb_column pos-top pos-center align_left column_parent col-lg-12 single-internal-gutter"><div class="uncol style-light"  ><div class="uncoltable"><div class="uncell no-block-padding" ><div class="uncont"><div class="uncode-single-media  text-left"><div class="single-wrapper" style="max-width: 100%;"><div class="tmb tmb-light  tmb-media-first tmb-media-last tmb-content-overlay tmb-no-bg"><div class="t-inside"><div class="t-entry-visual"><div class="t-entry-visual-tc"><div class="uncode-single-media-wrapper"><img fetchpriority="high" decoding="async" class="wp-image-674" src="https://tcfirenze.com/wp-content/uploads/2024/02/CFD-sostenibilita-scaled.jpg" width="1920" height="1080" alt="" srcset="https://tcfirenze.com/wp-content/uploads/2024/02/CFD-sostenibilita-scaled.jpg 1920w, https://tcfirenze.com/wp-content/uploads/2024/02/CFD-sostenibilita-300x169.jpg 300w, https://tcfirenze.com/wp-content/uploads/2024/02/CFD-sostenibilita-1024x576.jpg 1024w, https://tcfirenze.com/wp-content/uploads/2024/02/CFD-sostenibilita-768x432.jpg 768w, https://tcfirenze.com/wp-content/uploads/2024/02/CFD-sostenibilita-1536x864.jpg 1536w, https://tcfirenze.com/wp-content/uploads/2024/02/CFD-sostenibilita-2048x1152.jpg 2048w, https://tcfirenze.com/wp-content/uploads/2024/02/CFD-sostenibilita-350x197.jpg 350w, https://tcfirenze.com/wp-content/uploads/2024/02/CFD-sostenibilita-scaled-uai-720x405.jpg 720w, https://tcfirenze.com/wp-content/uploads/2024/02/CFD-sostenibilita-scaled-uai-1000x563.jpg 1000w, https://tcfirenze.com/wp-content/uploads/2024/02/CFD-sostenibilita-scaled-uai-1200x675.jpg 1200w, https://tcfirenze.com/wp-content/uploads/2024/02/CFD-sostenibilita-scaled-uai-1440x810.jpg 1440w, https://tcfirenze.com/wp-content/uploads/2024/02/CFD-sostenibilita-scaled-uai-1600x900.jpg 1600w" sizes="(max-width: 1920px) 100vw, 1920px" /></div>
					</div>
				</div></div></div></div></div></div></div></div></div></div><script id="script-row-unique-3" data-row="script-row-unique-3" type="text/javascript" class="vc_controls">UNCODE.initRow(document.getElementById("row-unique-3"));</script></div></div></div><div data-parent="true" class="vc_row row-container" id="row-unique-4"><div class="row limit-width row-parent"><div class="wpb_row row-inner"><div class="wpb_column pos-top pos-center align_left column_parent col-lg-12 single-internal-gutter"><div class="uncol style-light"  ><div class="uncoltable"><div class="uncell no-block-padding" ><div class="uncont"><div class="uncode_text_column" ></p>
<h2>Come la simulazione CFD può supportare la Strategia di Controllo della Contaminazione (CCS) e la Gestione del Rischio di Qualità (QRM)</h2>
<p>Il controllo della contaminazione è di primaria importanza nelle strutture farmaceutiche per garantire la qualità, la sicurezza del prodotto e la conformità agli standard normativi. La simulazione CFD svolge un ruolo fondamentale nel supportare CCS e QRM fornendo una comprensione completa dei modelli di flusso dell’aria, della dispersione delle particelle e delle prestazioni attese delle camere bianche. Attraverso una modellazione accurata, la simulazione CFD aiuta a individuare potenziali fonti di contaminazione, valutare l’efficacia dei sistemi di ventilazione e verificare la capacità del sistema di rispondere a possibili eventi di contaminazione. Visualizzando i modelli di flusso dell’aria e le traiettorie delle particelle, è possibile identificare aree con prestazioni inadeguate, portando all’implementazione di strategie di mitigazione mirate per ridurre i rischi di contaminazione. Inoltre, la simulazione CFD aiuta a ottimizzare i sistemi di filtrazione dell’aria, la disposizione delle camere bianche e le procedure operative per migliorare le misure di controllo della contaminazione complessive.</p>
</div></div></div></div></div></div><script id="script-row-unique-4" data-row="script-row-unique-4" type="text/javascript" class="vc_controls">UNCODE.initRow(document.getElementById("row-unique-4"));</script></div></div></div><div data-parent="true" class="vc_row row-container" id="row-unique-5"><div class="row limit-width row-parent"><div class="wpb_row row-inner"><div class="wpb_column pos-top pos-center align_left column_parent col-lg-12 single-internal-gutter"><div class="uncol style-light"  ><div class="uncoltable"><div class="uncell no-block-padding" ><div class="uncont"><div class="uncode_text_column" ></p>
<h2>Come la simulazione CFD può sostenere le iniziative di sostenibilità</h2>
<p>La simulazione della Dinamica dei Fluidi Computazionale (CFD) offre notevoli vantaggi nell’ottimizzazione del design del flusso d’aria e del consumo energetico associato nelle aree classificate delle strutture farmaceutiche. Mediante la modellazione accurata e l’analisi del flusso d’aria, la CFD consente di ridurre i processi ad elevato consumo energetico garantendo nel contempo l’efficienza operativa, contribuendo così agli sforzi di sostenibilità.</p>
<h3>Riduzione del consumo energetico nelle aree classificate in condizioni di progetto:</h3>
<p>La simulazione CFD consente l’ottimizzazione dei tassi di flusso d’aria di progetto nelle aree classificate, portando a sostanziali riduzioni del consumo energetico associato ai sistemi di ventilazione. Regolando con precisione i tassi di flusso d’aria di progetto, le strutture farmaceutiche possono garantire il mantenimento delle necessarie condizioni di camere bianche riducendo al minimo la spesa energetica non necessaria; ciò comporta risparmi economici e una riduzione della carbon footprint.</p>
<h3>Supporto a programmi di risparmio energetico in periodi non operativi:</h3>
<p>Grazie al processo di simulazione, la CFD può contribuire all’implementazione di programmi di risparmio energetico valutando e riducendo i tassi di flusso d’aria durante i periodi non operativi e senza personale. In condizioni non operative, i sistemi di HVAC per le aree classificate possono mantenere i livelli di prestazione richiesti con tassi di flusso d’aria ridotti. La simulazione CFD aiuta a anticipare le prestazioni dei sistemi HVAC in condizioni di flusso d’aria ridotto, identificando aree con prestazioni inadeguate e consentendo azioni correttive già nella fase di progettazione.</p>
<h3>Riduzione del carico energetico della ventilazione:</h3>
<p>Il consumo energetico per la ventilazione è proporzionale al cubo del volume d’aria fornito. Di conseguenza, anche riduzioni limitate nei tassi di flusso d’aria possono portare a una notevole diminuzione del consumo energetico dei sistemi di ventilazione. La riduzione della ventilazione contribuisce ai risparmi economici ma ha anche un impatto positive</p>
<h3>Miglioramento della sostenibilità attraverso la Dinamica dei Fluidi Computazionale (CFD):</h3>
<p>Sfruttando la simulazione CFD, le aziende farmaceutiche possono perseguire in modo proattivo gli obiettivi di sostenibilità. Ottimizzare i tassi di flusso dell’aria e attuare programmi di risparmio energetico si allinea agli impegni ambientali e riduce l’impronta di carbonio dell’impianto. Inoltre, una minore consumazione di energia contribuisce alla sostenibilità complessiva conservando le risorse naturali e riducendo le emissioni di gas serra.</p>
<p>&nbsp;</p>
<p>Esempio, Figura N.1<br />
Uso della CFD per l’ottimizzazione dei modelli di flusso d’aria in una sala di riempimento di grado B. Descrizione del caso</p>
</div></div></div></div></div></div><script id="script-row-unique-5" data-row="script-row-unique-5" type="text/javascript" class="vc_controls">UNCODE.initRow(document.getElementById("row-unique-5"));</script></div></div></div><div data-parent="true" class="vc_row row-container" id="row-unique-6"><div class="row limit-width row-parent"><div class="wpb_row row-inner"><div class="wpb_column pos-top pos-center align_left column_parent col-lg-4 single-internal-gutter"><div class="uncol style-light"  ><div class="uncoltable"><div class="uncell no-block-padding" ><div class="uncont"><div class="uncode-single-media  text-left"><div class="single-wrapper" style="max-width: 100%;"><div class="tmb tmb-light  tmb-media-first tmb-media-last tmb-content-overlay tmb-no-bg"><div class="t-inside"><div class="t-entry-visual"><div class="t-entry-visual-tc"><div class="uncode-single-media-wrapper"><img decoding="async" class="wp-image-668" src="https://tcfirenze.com/wp-content/uploads/2024/02/box-CFD-01.jpg" width="720" height="480" alt="" srcset="https://tcfirenze.com/wp-content/uploads/2024/02/box-CFD-01.jpg 720w, https://tcfirenze.com/wp-content/uploads/2024/02/box-CFD-01-300x200.jpg 300w, https://tcfirenze.com/wp-content/uploads/2024/02/box-CFD-01-350x233.jpg 350w" sizes="(max-width: 720px) 100vw, 720px" /></div>
					</div>
				</div></div></div></div></div></div></div></div></div></div><div class="wpb_column pos-top pos-center align_left column_parent col-lg-4 single-internal-gutter"><div class="uncol style-light"  ><div class="uncoltable"><div class="uncell no-block-padding" ><div class="uncont"><div class="uncode-single-media  text-left"><div class="single-wrapper" style="max-width: 100%;"><div class="tmb tmb-light  tmb-media-first tmb-media-last tmb-content-overlay tmb-no-bg"><div class="t-inside"><div class="t-entry-visual"><div class="t-entry-visual-tc"><div class="uncode-single-media-wrapper"><img decoding="async" class="wp-image-669" src="https://tcfirenze.com/wp-content/uploads/2024/02/box-CFD-02.jpg" width="720" height="480" alt="" srcset="https://tcfirenze.com/wp-content/uploads/2024/02/box-CFD-02.jpg 720w, https://tcfirenze.com/wp-content/uploads/2024/02/box-CFD-02-300x200.jpg 300w, https://tcfirenze.com/wp-content/uploads/2024/02/box-CFD-02-350x233.jpg 350w" sizes="(max-width: 720px) 100vw, 720px" /></div>
					</div>
				</div></div></div></div></div></div></div></div></div></div><div class="wpb_column pos-top pos-center align_left column_parent col-lg-4 single-internal-gutter"><div class="uncol style-light"  ><div class="uncoltable"><div class="uncell no-block-padding" ><div class="uncont"><div class="uncode-single-media  text-left"><div class="single-wrapper" style="max-width: 100%;"><div class="tmb tmb-light  tmb-media-first tmb-media-last tmb-content-overlay tmb-no-bg"><div class="t-inside"><div class="t-entry-visual"><div class="t-entry-visual-tc"><div class="uncode-single-media-wrapper"><img decoding="async" class="wp-image-670" src="https://tcfirenze.com/wp-content/uploads/2024/02/box-CFD-03.jpg" width="720" height="480" alt="" srcset="https://tcfirenze.com/wp-content/uploads/2024/02/box-CFD-03.jpg 720w, https://tcfirenze.com/wp-content/uploads/2024/02/box-CFD-03-300x200.jpg 300w, https://tcfirenze.com/wp-content/uploads/2024/02/box-CFD-03-350x233.jpg 350w" sizes="(max-width: 720px) 100vw, 720px" /></div>
					</div>
				</div></div></div></div></div></div></div></div></div></div><script id="script-row-unique-6" data-row="script-row-unique-6" type="text/javascript" class="vc_controls">UNCODE.initRow(document.getElementById("row-unique-6"));</script></div></div></div><div data-parent="true" class="vc_row row-container" id="row-unique-7"><div class="row limit-width row-parent"><div class="wpb_row row-inner"><div class="wpb_column pos-top pos-center align_left column_parent col-lg-12 single-internal-gutter"><div class="uncol style-light"  ><div class="uncoltable"><div class="uncell no-block-padding" ><div class="uncont"><div class="uncode_text_column" ><p>Problema: elevata quantità di aria proveniente dal RABS e dal soffitto HEPA da restituire al sistema HVAC ; analisi CFD preliminare dei modelli di flusso d’aria all’interno della stanza -&gt; difficoltà a bilanciare il sistema, rischio di vortici.Soluzione: Azioni correttive e ottimizzazione dei flussi attraverso l’introduzione di un’ulteriore parete d’aria e la settorizzazione di due pareti d’aria -&gt; bilanciamento virtuale delle portate d’aria di ritorno.</p>
<p>&nbsp;</p>
<h2>Risultati della simulazione CFD</h2>
<p>
</div></div></div></div></div></div><script id="script-row-unique-7" data-row="script-row-unique-7" type="text/javascript" class="vc_controls">UNCODE.initRow(document.getElementById("row-unique-7"));</script></div></div></div><div data-parent="true" class="vc_row row-container" id="row-unique-8"><div class="row limit-width row-parent"><div class="wpb_row row-inner"><div class="wpb_column pos-top pos-center align_left column_parent col-lg-4 single-internal-gutter"><div class="uncol style-light"  ><div class="uncoltable"><div class="uncell no-block-padding" ><div class="uncont"><div class="uncode-single-media  text-left"><div class="single-wrapper" style="max-width: 100%;"><div class="tmb tmb-light  tmb-media-first tmb-media-last tmb-content-overlay tmb-no-bg"><div class="t-inside"><div class="t-entry-visual"><div class="t-entry-visual-tc"><div class="uncode-single-media-wrapper"><img decoding="async" class="wp-image-671" src="https://tcfirenze.com/wp-content/uploads/2024/02/cross-section.jpg" width="720" height="480" alt="" srcset="https://tcfirenze.com/wp-content/uploads/2024/02/cross-section.jpg 720w, https://tcfirenze.com/wp-content/uploads/2024/02/cross-section-300x200.jpg 300w, https://tcfirenze.com/wp-content/uploads/2024/02/cross-section-350x233.jpg 350w" sizes="(max-width: 720px) 100vw, 720px" /></div>
					</div>
				</div></div></div></div></div></div></div></div></div></div><div class="wpb_column pos-top pos-center align_left column_parent col-lg-4 single-internal-gutter"><div class="uncol style-light"  ><div class="uncoltable"><div class="uncell no-block-padding" ><div class="uncont"><div class="uncode-single-media  text-left"><div class="single-wrapper" style="max-width: 100%;"><div class="tmb tmb-light  tmb-media-first tmb-media-last tmb-content-overlay tmb-no-bg"><div class="t-inside"><div class="t-entry-visual"><div class="t-entry-visual-tc"><div class="uncode-single-media-wrapper"><img decoding="async" class="wp-image-673" src="https://tcfirenze.com/wp-content/uploads/2024/02/before-corrective-action.jpg" width="720" height="480" alt="" srcset="https://tcfirenze.com/wp-content/uploads/2024/02/before-corrective-action.jpg 720w, https://tcfirenze.com/wp-content/uploads/2024/02/before-corrective-action-300x200.jpg 300w, https://tcfirenze.com/wp-content/uploads/2024/02/before-corrective-action-350x233.jpg 350w" sizes="(max-width: 720px) 100vw, 720px" /></div>
					</div>
				</div></div></div></div></div></div></div></div></div></div><div class="wpb_column pos-top pos-center align_left column_parent col-lg-4 single-internal-gutter"><div class="uncol style-light"  ><div class="uncoltable"><div class="uncell no-block-padding" ><div class="uncont"><div class="uncode-single-media  text-left"><div class="single-wrapper" style="max-width: 100%;"><div class="tmb tmb-light  tmb-media-first tmb-media-last tmb-content-overlay tmb-no-bg"><div class="t-inside"><div class="t-entry-visual"><div class="t-entry-visual-tc"><div class="uncode-single-media-wrapper"><img decoding="async" class="wp-image-672" src="https://tcfirenze.com/wp-content/uploads/2024/02/after-corrective-action.jpg" width="720" height="480" alt="" srcset="https://tcfirenze.com/wp-content/uploads/2024/02/after-corrective-action.jpg 720w, https://tcfirenze.com/wp-content/uploads/2024/02/after-corrective-action-300x200.jpg 300w, https://tcfirenze.com/wp-content/uploads/2024/02/after-corrective-action-350x233.jpg 350w" sizes="(max-width: 720px) 100vw, 720px" /></div>
					</div>
				</div></div></div></div></div></div></div></div></div></div><script id="script-row-unique-8" data-row="script-row-unique-8" type="text/javascript" class="vc_controls">UNCODE.initRow(document.getElementById("row-unique-8"));</script></div></div></div><div data-parent="true" class="vc_row row-container" id="row-unique-9"><div class="row limit-width row-parent"><div class="wpb_row row-inner"><div class="wpb_column pos-top pos-center align_left column_parent col-lg-12 single-internal-gutter"><div class="uncol style-light"  ><div class="uncoltable"><div class="uncell no-block-padding" ><div class="uncont"><div class="uncode_text_column" ><p>In generale: i modelli di flusso d’aria dopo le azioni correttive sono più uniformi.I vortici mostrati nella sezione sono eliminati e l’unidirezionalità del flusso d’aria è molto più presente nello spazio della stanza -&gt; il rischio di riflusso dal livello del pavimento alle aree critiche (aree di sosta, uscite RABS aperte e mouse-hole) è ridotto.<br />
Allo stesso tempo, questa correzione aerodinamica può favorire la riduzione della portata d’aria della stanza in condizioni di riposo.</p>
<p>&nbsp;</p>
<h2>Conclusioni</h2>
<p>La simulazione CFD si è affermata come uno strumento potente per sostenere strategie di controllo delle contaminazioni, gestione del rischio di qualità e iniziative di sostenibilità nelle strutture farmaceutiche. Predicendo con precisione il flusso dei fluidi, il trasferimento di calore e la dispersione delle contaminazioni, la simulazione CFD consente alle organizzazioni di prendere decisioni informate, ottimizzare i processi e garantire la produzione di prodotti farmaceutici sicuri ed efficaci.</p>
</div></div></div></div></div></div><script id="script-row-unique-9" data-row="script-row-unique-9" type="text/javascript" class="vc_controls">UNCODE.initRow(document.getElementById("row-unique-9"));</script></div></div></div>
</div><p>L'articolo <a href="https://tcfirenze.com/come-la-simulazione-cfd-puo-supportare-c-c-s-q-r-m-e-sostenibilita-nelle-strutture-farmaceutiche/">Come la simulazione CFD può supportare C.C.S., Q.R.M. e sostenibilità nelle strutture farmaceutiche</a> proviene da <a href="https://tcfirenze.com">Techniconsult</a>.</p>